Load Characteristic Model: MOTORX

 

Model Equations and/or Block Diagrams

Parameters:

MBase MBase: MBase of Load Model
AppliesTo 0 means it applies to all, 1 means it applies to only the constant power part of the load
Pul Pul: Fraction of constant-power load to be represented by this motor model (between 1.0 and 0.0)
Rs Rs: Stator winding resistance, p.u.
Xs Xs: Stator winding reactance, p.u.
Xm Xm: Magnetizing reactance, p.u.
R1 R1: Rotor resistance, p.u.
X1 X1: Rotor leakage reactance, p.u.
R2 R2: Rotor resistance, p.u. (0 for single cage motor)
X2 X2: Rotor leakage reactance, p.u. (0 for single cage motor)
H H: Inertia constant, sec.
D D: Damping factor, p.u.
Vt Vt: Voltage threshold for tripping, p.u.
Tv Tv: Voltage trip pickup time, sec.
Tbkr Tbkr: Circuit breaker operating time, sec.
Acc Acc: Acceleration factor for initialization
ndelt ndelt: Time step subdivision factor.
wdelt wdelt: Speed threshold for subdividing time step, p.u.
pfact pfact: Mbase Multiplier